DEHNpatch

Surge Arrester

Patch cable with built-in surge protection Cat. 6 according to ISO/IEC 11801 CAT 6A in the channel according to ANSI/TIA/EIA-568 Power over Ethernet (PoE+ according to IEEE 802.3at) Easy to retrofit

Description

Designed as a patch cable, DEHNpatch can be easily installed in new installations or retrofitted into existing installations. DEHNpatch is installed between the patch panel and the active component (a switch for example) instead of the conventional patch cable. The snap-in mechanism of the supporting foot allows the device to be safely earthed via the DIN rail. For single application, DEHNpatch comes with a piece of DIN rail and a fixing device. A mounting set is also available as accessory for multiple application in 19“ distribution boards. Fulfilling the requirements of Category 6, DEHNpatch can be universally used for all data services up to nominal voltages of 57 V. Both existing applications in offices and industry such as Gigabit Ethernet, ATM or ISDN as well as future services such as Voice over IP and Power over Ethernet can be protected. Due to its fully shielded design, DEHNpatch can be used in shielded and unshielded networks. Its width is similar to that of an RJ45 socket, allowing up to 24 devices to be installed next to one another in one series and to be integrated into a 19" rack. DEHNpatch is available with a total patch cable length of 3 m and 5 m (other lengths can be provided available on request).

Detail 1

With RJ45 sockets, fully shielded.

Detail 2

For DIN rail and wall mounting.

Detail 3

Patch cable version, fully shielded.

Detail 4

Mounting set (DIN rail, distance bolts) for 19” mounting sections available as accessory.

Specification

Type DPA M CAT6 RJ45S 48
Part No. 929 100
SPD class T
Nominal voltage (UN) 48 V
Max. continuous operating d.c. voltage (Uc) 48 V
Max. continuous operating a.c. voltage (Uc) 34 V
Max. continuous operating d.c. voltage pair-pair (PoE) (Uc) 57 V
Nominal current (IL) 1 A
D1 Lightning impulse current (10/350 µs) per line (Iimp) 1 kA
C2 Nominal discharge current (8/20 µs) line-line (In) 150 A
C2 Nominal discharge current (8/20 µs) line-PG (In) 2.5 kA
C2 Total nominal discharge current (8/20 µs) line-PG (In) 10 kA
C2 Nominal discharge current (8/20 µs) pair-pair (PoE) (In) 150 A
Voltage protection level line-line for In C2 (UP) ≤ 190 V
Voltage protection level line-PG for In C2 (UP) ≤ 600 V
Voltage protection level line-line for In C2 (PoE) (UP) ≤ 600 V
Voltage protection level line-line at 1 kV/µs C3 (UP) ≤ 145 V
Voltage protection level line-PG at 1 kV/µs C3 (UP) ≤ 500 V
Voltage protection level pair-pair at 1 kV/µs C3 (PoE) (UP) ≤ 600 V
Insertion loss at 250 MHz ≤ 2 dB
Capacitance line-line (C) ≤ 165 pF
Capacitance line-PG (C) ≤ 255 pF
Operating temperature range (TU) -20 °C ... +60 °C
Degree of protection IP 20
For mounting on 35 mm DIN rails acc. to EN 60715
Connection (input / output) RJ45 connecting line / RJ45 connecting line
Pinning 1/2, 3/6, 4/5, 7/8
Connecting line A = approx. 0.5 m, G = approx. 3 m *)
Connector Stewart 39 series
Earthing via 35 mm DIN rail acc. to EN 60715
Enclosure material zinc die-casting
Colour bare surface
Test standards IEC 61643-21 / EN 61643-21
Transmission class according to ISO/IEC 11801 Cat. 6
Transmission class according to EN 50173-1 Class EA
Transmission class according to ANSI/TIA/EIA-568 cat. 6A in the channel
Approvals GHMT, GOST
Accessories fixing material
Weight 244 g
GTIN 4.01E+12
PU 1 pc(s)
Product Specifications (PDF)